Electrical cables
Explore individual product photographs, size variants and technical data directly on this page.

Product video
Watch on YouTubeElectrical cables
BYJ
BYJ: copper conductor with cross-linked polyolefin insulation. WDZA-BYJ, WDZA-BYJ-105, WDZA-BYJ-125; JB/T 10491-2022.

| Cross section (mm²) | Conductor class | Outside diameter (mm) | 20°C resistance (Ω/km) | Ampacity (A) |
|---|---|---|---|---|
| 0.75 | 1 | 2.2 | 24.5 | 18 |
| 0.75 | 2 | 2.3 | 24.5 | 18 |
| 1.0 | 1 | 2.3 | 18.1 | 22 |
| 1.0 | 2 | 2.5 | 18.1 | 22 |
| 1.5 | 1 | 2.8 | 12.1 | 28 |
| 1.5 | 2 | 3 | 12.1 | 28 |
| 2.5 | 1 | 3.4 | 7.41 | 41 |
| 2.5 | 2 | 3.6 | 7.41 | 41 |
| 4 | 1 | 3.9 | 4.61 | 54 |
| 4 | 2 | 4.1 | 4.61 | 54 |
| 6 | 1 | 4.4 | 3.08 | 68 |
| 6 | 2 | 4.7 | 3.08 | 68 |
| 10 | 2 | 6 | 1.83 | 93 |
| 16 | 2 | 7.1 | 1.15 | 120 |
| 25 | 2 | 8.8 | 0.727 | 155 |
| 35 | 2 | 9.9 | 0.524 | 195 |
| 50 | 2 | 11.7 | 0.387 | 235 |
| 70 | 2 | 13.4 | 0.268 | 295 |
| 95 | 2 | 15.7 | 0.193 | 370 |
| 120 | 2 | 17.3 | 0.153 | 430 |
| 150 | 2 | 19.2 | 0.124 | 495 |
| 185 | 2 | 21.4 | 0.0991 | 570 |
| 240 | 2 | 24.5 | 0.0754 | 680 |
| 300 | 2 | 27.2 | 0.0601 | 790 |
BVV
BVV: copper conductor with PVC insulation and round PVC sheath. JB/T 8734.2-2016; ZC-BVV also follows GB/T 19666-2019. 300/500 V.

| Cross section (mm²) | Conductor class | Outside diameter (mm) | 20°C resistance (Ω/km) | Ampacity (A) |
|---|---|---|---|---|
| 0.75 | 1 | 3.8 | 24.5 | 14 |
| 0.75 | 2 | 3.9 | 24.5 | 14 |
| 1.0 | 1 | 3.9 | 18.1 | 16 |
| 1.0 | 2 | 4.1 | 18.1 | 16 |
| 1.5 | 1 | 4.4 | 12.1 | 21 |
| 1.5 | 2 | 4.6 | 12.1 | 21 |
| 2.5 | 1 | 5 | 7.41 | 25 |
| 2.5 | 2 | 5.2 | 7.41 | 25 |
| 4 | 1 | 5.7 | 4.61 | 38 |
| 4 | 2 | 5.9 | 4.61 | 38 |
| 6 | 1 | 6.2 | 3.08 | 49 |
| 6 | 2 | 6.5 | 3.08 | 49 |
| 10 | 2 | 7.8 | 1.83 | 68 |
| 16 | 2 | 8.9 | 1.15 | 91 |
| 25 | 2 | 10.8 | 0.727 | 120 |
| 35 | 2 | 12.1 | 0.524 | 150 |
| 50 | 2 | 14.3 | 0.387 | 180 |
| 70 | 2 | 16.2 | 0.268 | 230 |
| 95 | 2 | 18.7 | 0.193 | 290 |
| 120 | 2 | 20.5 | 0.153 | 335 |
| 150 | 2 | 22.8 | 0.124 | 390 |
| 185 | 2 | 25.2 | 0.0991 | 450 |
| 240 | 2 | 27.7 | 0.0754 | 545 |
| 300 | 2 | 30.6 | 0.0601 | 630 |
| 400 | 2 | 34.3 | 0.047 | 735 |
Additional cable series
EV-SS / EV-S90S90 / EV-SSPS / EV-S90S90PS90
EV charging cable: GB/T 33594-2017, 450/750 V. Type S: −25…+70°C; type S90: −40…+90°C.
| Cores × section (mm²) | Min. diameter (mm) | Max. diameter (mm) | 20°C resistance (Ω/km) | Ampacity (A) |
|---|---|---|---|---|
| 3x1.0 | 10.9 | 14.0 | 19.5 | 16 |
| 3x2.5 | 12.6 | 16.1 | 7.98 | 25 |
| 3x4 | 14.4 | 18.4 | 4.95 | 38 |
| 3x6 | 15.8 | 20.2 | 3.30 | 49 |
| 3x10 | 17.6 | 22.3 | 1.91 | 65 |
| 3x16 | 20.1 | 25.4 | 1.21 | 84 |
| 3x25 | 24.0 | 30.4 | 0.78 | 110 |
| 3x35 | 27.7 | 35.0 | 0.554 | 135 |
| 3x50 | 32.4 | 40.9 | 0.386 | 170 |
| 3x70 | 37.1 | 46.8 | 0.272 | 215 |
| 4x1.0 | 11.9 | 15.2 | 19.5 | 16 |
| 4x2.5 | 13.7 | 17.5 | 7.98 | 28 |
| 4x4 | 16.0 | 20.4 | 4.95 | 37 |
| 4x6 | 17.5 | 22.2 | 3.30 | 47 |
| 4x10 | 19.7 | 25.0 | 1.91 | 65 |
| 4x16 | 22.5 | 28.6 | 1.21 | 84 |
| 4x50 | 36.2 | 45.6 | 0.386 | 170 |
| 4x70 | 41.4 | 52.1 | 0.272 | 215 |
| 5x1.0 | 12.9 | 16.4 | 19.5 | 16 |
| 5x1.5 | 13.6 | 17.4 | 13.3 | 22 |
| 5x2.5 | 14.9 | 19.0 | 7.98 | 28 |
| 5x4 | 17.6 | 22.3 | 4.95 | 37 |
| 5x6 | 19.3 | 24.5 | 3.30 | 47 |
| 5x16 | 25.0 | 31.7 | 1.21 | 84 |
| 5x25 | 30.7 | 38.8 | 0.78 | 110 |
| 5x35 | 34.2 | 43.1 | 0.554 | 135 |
| 5x50 | 40.2 | 50.6 | 0.386 | 170 |
| 5x70 | 45.9 | 57.7 | 0.272 | 215 |
EV-RSS / EV-RS90S90 / EV-RSSPS / EV-RS90S90PS90
EV charging cable: GB/T 33594-2017, 450/750 V. Type S: −25…+70°C; type S90: −40…+90°C.
| Cores × section (mm²) | Min. diameter (mm) | Max. diameter (mm) | 20°C resistance (Ω/km) | Ampacity (A) |
|---|---|---|---|---|
| 3x1.0 | 12.3 | 15.7 | 19.5 | 16 |
| 3x2.5 | 13.9 | 17.8 | 7.98 | 25 |
| 3x4 | 16.1 | 20.5 | 4.95 | 38 |
| 3x6 | 17.4 | 22.1 | 3.30 | 49 |
| 3x10 | 19.3 | 24.5 | 1.91 | 65 |
| 3x16 | 21.6 | 27.4 | 1.21 | 84 |
| 3x25 | 25.7 | 32.5 | 0.78 | 110 |
| 3x35 | 29.7 | 37.6 | 0.554 | 135 |
| 3x50 | 34.5 | 43.4 | 0.386 | 170 |
| 3x70 | 39.2 | 49.3 | 0.272 | 215 |
| 4x1.0 | 13.2 | 16.9 | 19.5 | 16 |
| 4x2.5 | 15.3 | 19.4 | 7.98 | 28 |
| 4x4 | 17.6 | 22.3 | 4.95 | 37 |
| 4x16 | 24.3 | 30.7 | 1.21 | 84 |
| 4x25 | 29.2 | 36.8 | 0.78 | 110 |
| 4x70 | 43.2 | 54.4 | 0.272 | 215 |
| 5x1.5 | 15.2 | 19.3 | 13.3 | 22 |
| 5x2.5 | 16.4 | 20.9 | 7.98 | 28 |
| 5x4 | 19.3 | 24.5 | 4.95 | 37 |
| 5x6 | 20.8 | 26.4 | 3.30 | 47 |
| 5x10 | 23.6 | 29.9 | 1.91 | 65 |
| 5x16 | 26.8 | 33.8 | 1.21 | 84 |
| 5x25 | 32.5 | 41.0 | 0.78 | 110 |
| 5x35 | 36.2 | 45.6 | 0.554 | 135 |
| 5x50 | 42.0 | 52.9 | 0.386 | 170 |
| 5x70 | 48.1 | 60.5 | 0.272 | 215 |
RVV
Flexible copper cable with PVC insulation and sheath, 300/500 V.
| Cores × section (mm²) | Outside diameter (mm) | 20°C resistance (Ω/km) | Ampacity (A) |
|---|---|---|---|
| 2x1.0 | 7 | 19.5 | 16 |
| 2x4.0 | 11.7 | 4.95 | 38 |
| 2x6.0 | 13.2 | 3.30 | 49 |
| 2x10 | 16.3 | 1.91 | 68 |
| 3x0.75 | 7.2 | 26.0 | 14 |
| 3x2.5 | 10.9 | 7.98 | 25 |
| 3x6.0 | 14.3 | 3.30 | 49 |
| 4x4.0 | 13.9 | 4.95 | 38 |
| 4x6.0 | 15.7 | 3.30 | 49 |
| 5x2.5 | 13.2 | 7.98 | 25 |
| 5x4.0 | 15.5 | 4.95 | 38 |
| 5x6.0 | 18.6 | 3.30 | 49 |
YJV / YJLHV
XLPE insulated power cable, 600/1000 V, GB/T 12706.1-2020. Version 22 has steel-tape armour.
| Cores × section (mm²) | Outside diameter (mm) |
|---|---|
| 3x16+1x10 | 18.6 |
| 3x25+1x16 | 22.1 |
| 3x35+1x16 | 23.9 |
| 3x50+1x25 | 27.4 |
| 3x95+1x50 | 36.0 |
| 3x120+1x70 | 40.3 |
| 3x150+1x70 | 44.2 |
| 3x240+1x120 | 54.7 |
| 3x300+1x150 | 60.7 |
| 3x400+1x185 | 68.4 |
| 3x16+2x10 | 19.9 |
| 3x25+2x16 | 23.5 |
| 3x35+2x16 | 25.2 |
| 3x50+2x25 | 29.3 |
| 3x70+2x35 | 33.9 |
| 3x95+2x50 | 38.4 |
| 3x120+2x70 | 43.3 |
| 3x150+2x70 | 46.8 |
| 3x240+2x120 | 58.0 |
| 3x300+2x150 | 64.4 |
| 4x10+1x6 | 17.7 |
| 4x16+1x10 | 20.4 |
| 4x25+1x16 | 24.4 |
| 4x50+1x25 | 30.6 |
| 4x70+1x35 | 35.9 |
| 4x120+1x70 | 45.3 |
| 4x150+1x70 | 49.8 |
| 4x240+1x120 | 61.6 |
| 4x300+1x150 | 68.3 |
YJV22 / YJLHV22
XLPE insulated power cable, 600/1000 V, GB/T 12706.1-2020. Version 22 has steel-tape armour.
| Cores × section (mm²) | Outside diameter (mm) |
|---|---|
| 3x16+1x10 | 20.6 |
| 3x25+1x16 | 24.1 |
| 3x35+1x16 | 25.9 |
| 3x50+1x25 | 29.4 |
| 3x70+1x35 | 34.1 |
| 3x95+1x50 | 39.8 |
| 3x120+1x70 | 44.3 |
| 3x150+1x70 | 48.2 |
| 3x240+1x120 | 59.1 |
| 3x300+1x150 | 64.9 |
| 3x400+1x185 | 72.8 |
| 3x50+2x25 | 31.3 |
| 3x70+2x35 | 35.9 |
| 3x95+2x50 | 42.2 |
| 3x120+2x70 | 47.3 |
| 3x150+2x70 | 50.8 |
| 3x240+2x120 | 62.4 |
| 3x300+2x150 | 68.8 |
| 4x16+1x10 | 22.4 |
| 4x35+1x16 | 28.6 |
| 4x50+1x25 | 32.8 |
| 4x70+1x35 | 39.1 |
| 4x95+1x50 | 44.3 |
| 4x120+1x70 | 49.1 |
| 4x150+1x70 | 54.2 |
| 4x240+1x120 | 66.0 |
| 4x300+1x150 | 72.7 |
| 4x400+1x185 | 82.9 |
Household wiring series
BY
WDZA-BY copper conductor with polyolefin insulation. GB/T 19666-2019 / Q/LS 108-2024.

| Cross section (mm²) | Conductor class | Outside diameter (mm) | 20°C resistance (Ω/km) | 70°C insulation resistance (MΩ·km) | Catalogue ampacity (A) | Reference mass (kg/km) |
|---|---|---|---|---|---|---|
| 0.75 | 1 | 2.2 | 24.5 | 0.012 | 14 | 11 |
| 0.75 | 2 | 2.3 | 24.5 | 0.014 | 14 | 11 |
| 1 | 1 | 2.3 | 18.1 | 0.011 | 16 | 14 |
| 1 | 2 | 2.5 | 18.1 | 0.013 | 16 | 14 |
| 1.5 | 1 | 2.8 | 12.1 | 0.011 | 21 | 20 |
| 1.5 | 2 | 3 | 12.1 | 0.01 | 21 | 20 |
| 2.5 | 1 | 3.4 | 7.41 | 0.01 | 25 | 32 |
| 2.5 | 2 | 3.6 | 7.41 | 0.009 | 25 | 32 |
| 4 | 1 | 3.9 | 4.61 | 0.0085 | 38 | 46 |
| 4 | 2 | 4.1 | 4.61 | 0.0077 | 38 | 46 |
| 6 | 1 | 4.4 | 3.08 | 0.007 | 49 | 66 |
| 6 | 2 | 4.7 | 3.08 | 0.0065 | 49 | 66 |
| 10 | 2 | 6 | 1.83 | 0.0065 | 68 | 115 |
| 16 | 2 | 7.1 | 1.15 | 0.005 | 91 | 173 |
| 25 | 2 | 8.8 | 0.727 | 0.005 | 120 | 269 |
| 35 | 2 | 9.9 | 0.524 | 0.004 | 150 | 370 |
RY
WDZA-RY flexible copper conductor with polyolefin insulation. GB/T 19666-2019 / Q/LS 108-2024.

| Cross section (mm²) | Conductor class | Outside diameter (mm) | 20°C resistance (Ω/km) | 70°C insulation resistance (MΩ·km) | Catalogue ampacity (A) | Reference mass (kg/km) |
|---|---|---|---|---|---|---|
| 0.75 | 5 | 2.3 | 26 | 0.011 | 14 | 12 |
| 1 | 5 | 2.5 | 19.5 | 0.01 | 16 | 15 |
| 1.5 | 5 | 3 | 13.3 | 0.01 | 21 | 21 |
| 2.5 | 5 | 3.9 | 7.89 | 0.009 | 25 | 34 |
| 4 | 5 | 4.6 | 4.95 | 0.007 | 38 | 50 |
| 6 | 5 | 5.3 | 3.3 | 0.006 | 49 | 71 |
| 10 | 5 | 6.8 | 1.91 | 0.0056 | 68 | 118 |
| 16 | 5 | 7.9 | 1.21 | 0.0046 | 91 | 176 |
| 25 | 5 | 9.8 | 0.78 | 0.0044 | 120 | 275 |
| 35 | 5 | 11 | 0.554 | 0.0038 | 150 | 366 |
BYJR
WDZA-BYJR, WDZA-BYJR-105 and WDZA-BYJR-125 flexible cable with cross-linked polyolefin insulation. JB/T 10491-2022.

| Cross section (mm²) | Conductor class | Outside diameter (mm) | 20°C resistance (Ω/km) | 70°C insulation resistance (MΩ·km) | Catalogue ampacity (A) | Reference mass (kg/km) |
|---|---|---|---|---|---|---|
| 1 | 2 | 3.1 | 18.1 | 0.01 | 14 | 17 |
| 1.5 | 2 | 3.4 | 12.1 | 0.01 | 21 | 23 |
| 2.5 | 2 | 4.1 | 7.41 | 0.01 | 33 | 35 |
| 4 | 2 | 4.8 | 4.61 | 0.0079 | 48 | 52 |
| 6 | 2 | 5.3 | 3.08 | 0.0068 | 68 | 72 |
| 10 | 2 | 7.3 | 1.83 | 0.0066 | 114 | 124 |
| 16 | 2 | 8.6 | 1.15 | 0.0054 | 171 | 182 |
| 25 | 2 | 10.2 | 0.727 | 0.0051 | 266 | 292 |
| 35 | 2 | 11.7 | 0.524 | 0.0043 | 365 | 381 |
RV
Flexible copper PVC-insulated wire, 60227 IEC 02/06 (RV), including ZC variants. GB/T 5023.3-2008 / IEC 60227-3:1997.

| Cross section (mm²) | Conductor class | Outside diameter (mm) | 20°C resistance (Ω/km) | 70°C insulation resistance (MΩ·km) | Catalogue ampacity (A) | Reference mass (kg/km) |
|---|---|---|---|---|---|---|
| 0.75 | 5 | 2.3 | 26 | 0.014 | 14 | 12 |
| 1 | 5 | 2.5 | 19.5 | 0.011 | 16 | 15 |
| 1.5 | 5 | 3 | 13.3 | 0.01 | 21 | 21 |
| 2.5 | 5 | 3.9 | 7.89 | 0.009 | 25 | 34 |
| 4 | 5 | 4.6 | 4.95 | 0.007 | 38 | 50 |
| 6 | 5 | 5.3 | 3.3 | 0.006 | 49 | 71 |
| 10 | 5 | 6.8 | 1.91 | 0.0056 | 68 | 118 |
| 16 | 5 | 7.9 | 1.21 | 0.0046 | 91 | 176 |
| 25 | 5 | 9.8 | 0.78 | 0.0044 | 120 | 275 |
| 35 | 5 | 11 | 0.554 | 0.0038 | 150 | 366 |
| 50 | 5 | 13.7 | 0.386 | 0.0037 | 180 | 538 |
| 70 | 5 | 15.7 | 0.272 | 0.0032 | 230 | 735 |
| 95 | 5 | 18.3 | 0.206 | 0.0032 | 290 | 921 |
| 120 | 5 | 20.3 | 0.161 | 0.0029 | 335 | 1158 |
| 150 | 5 | 23.2 | 0.129 | 0.0029 | 390 | 1447 |
| 185 | 5 | 25.1 | 0.106 | 0.0029 | 450 | 1766 |
| 240 | 5 | 34.7 | 0.0801 | 0.0028 | 545 | 2360 |
RVS
Twisted flexible copper PVC-insulated wire, 300/300 V. JB/T 8734.3-2016; ZC-RVS additionally follows GB/T 19666-2019.

| Cross section (mm²) | Conductor class | Outside diameter (mm) | 20°C resistance (Ω/km) | 70°C insulation resistance (MΩ·km) | Catalogue ampacity (A) | Reference mass (kg/km) |
|---|---|---|---|---|---|---|
| 2×0.75 | 6 | 5.72 | 26 | 0.013 | 12 | 22 |
| 2×1.0 | 6 | 6.2 | 19.5 | 0.012 | 14 | 30 |
| 2×1.5 | 6 | 6.86 | 13.3 | 0.009 | 18 | 37 |
| 2×2.5 | 6 | 8.26 | 7.89 | 0.009 | 25 | 48 |
| 2×4.0 | 6 | 9.3 | 4.95 | 0.007 | 33 | 71 |
| 2×6.0 | 6 | 11.9 | 3.3 | 0.006 | 42 | 105 |
BV / BVR
BV
PVC insulated copper wire, 60227 IEC 01/05 (BV), including ZC versions. GB/T 5023.3-2008 / IEC 60227-3:1997; ZC additionally GB/T 19666-2019.

| Cross section (mm²) | Conductor class | Outside diameter (mm) | 20°C resistance (Ω/km) | 70°C insulation resistance (MΩ·km) | Catalogue ampacity (A) | Standard/ZR mass (kg/km) | NH mass (kg/km) |
|---|---|---|---|---|---|---|---|
| 0.75 | 1 | 2.2 | 24.5 | 0.012 | 14 | 11 | 15 |
| 0.75 | 2 | 2.3 | 24.5 | 0.014 | 14 | 11 | 15 |
| 1 | 1 | 2.3 | 18.1 | 0.011 | 16 | 14 | 18 |
| 1 | 2 | 2.5 | 18.1 | 0.013 | 16 | 14 | 18 |
| 1.5 | 1 | 2.8 | 12.1 | 0.011 | 21 | 20 | 25 |
| 1.5 | 2 | 3 | 12.1 | 0.01 | 21 | 20 | 25 |
| 2.5 | 1 | 3.4 | 7.41 | 0.01 | 25 | 32 | 37 |
| 2.5 | 2 | 3.6 | 7.41 | 0.009 | 25 | 32 | 37 |
| 4 | 1 | 3.9 | 4.61 | 0.0085 | 38 | 46 | 53 |
| 4 | 2 | 4.1 | 4.61 | 0.0077 | 38 | 46 | 53 |
| 6 | 1 | 4.4 | 3.08 | 0.007 | 49 | 66 | 74 |
| 6 | 2 | 4.7 | 3.08 | 0.0065 | 49 | 66 | 74 |
| 10 | 2 | 6 | 1.83 | 0.0065 | 68 | 115 | 117 |
| 16 | 2 | 7.1 | 1.15 | 0.005 | 91 | 173 | 174 |
| 25 | 2 | 8.8 | 0.727 | 0.005 | 120 | 269 | 269 |
| 35 | 2 | 9.9 | 0.524 | 0.004 | 150 | 370 | 368 |
| 50 | 2 | 11.7 | 0.387 | 0.0045 | 180 | 493 | 489 |
| 70 | 2 | 13.4 | 0.268 | 0.0035 | 230 | 694 | 687 |
| 95 | 2 | 15.7 | 0.193 | 0.0035 | 290 | 959 | 948 |
| 120 | 2 | 17.3 | 0.153 | 0.0032 | 335 | 1182 | 1174 |
| 150 | 2 | 19.2 | 0.124 | 0.0032 | 390 | 1453 | 1432 |
| 185 | 2 | 21.4 | 0.0991 | 0.0032 | 450 | 1820 | 1795 |
| 240 | 2 | 24.5 | 0.0754 | 0.0032 | 545 | 2373 | 2351 |
| 300 | 2 | 27.2 | 0.0601 | 0.003 | 630 | 2966 | 2926 |
| 400 | 2 | 30.7 | 0.047 | 0.0028 | 735 | 3785 | 3736 |
BVR
Flexible copper PVC-insulated wire, 450/750 V, JB/T 8734.2-2016; ZC-BVR additionally GB/T 19666-2019.

| Cross section (mm²) | Outside diameter (mm) | 20°C resistance (Ω/km) | 70°C insulation resistance (MΩ·km) | Catalogue ampacity (A) | Standard/ZR mass (kg/km) |
|---|---|---|---|---|---|
| 0.75 | 2.5 | 24.5 | 0.013 | 14 | 15.2 |
| 1 | 2.7 | 18.1 | 0.012 | 16 | 15.8 |
| 1.5 | 3 | 12.1 | 0.011 | 21 | 21.1 |
| 2.5 | 3.7 | 7.41 | 0.011 | 25 | 33.6 |
| 4 | 4.2 | 4.61 | 0.009 | 38 | 49.6 |
| 6 | 4.8 | 3.08 | 0.0084 | 49 | 70.6 |
| 10 | 6.7 | 1.83 | 0.0072 | 68 | 121.9 |
| 16 | 7.8 | 1.15 | 0.0062 | 91 | 175.7 |
| 25 | 10.1 | 0.727 | 0.0058 | 120 | 287.3 |
| 35 | 11.1 | 0.524 | 0.0052 | 150 | 377.4 |
| 50 | 13 | 0.387 | 0.0051 | 180 | 518.4 |
| 70 | 15.4 | 0.268 | 0.0045 | 230 | 719.7 |
| 95 | 17.5 | 0.193 | 0.0044 | 290 | 961.9 |
| 120 | 19.2 | 0.153 | 0.004 | 335 | 1187.4 |
| 150 | 21.7 | 0.124 | 0.004 | 390 | 1463.6 |
| 185 | 24 | 0.0991 | 0.004 | 450 | 1830.7 |
Electrical wires
Copper and aluminium conductors, PVC insulation, round or flat sheath, rigid and flexible versions. Flame-retardant ZC and fire-resistant ZCN variants are listed separately.
| Model / variant | Rated voltage |
|---|---|
| 60227IEC01 (BV) | 450/750 V |
| 60227IEC05 (BV) | 300/500 V |
| 60227IEC07 (BV-90) | 300/500 V |
| BVV | 300/500 V |
| BLV | 450/750 V |
| BVR | 450/750 V |
| BLVV | 300/500 V |
| BVVB | 300/500 V |
| BLVVB | 300/500 V |
| 60227IEC02 (RV) | 450/750 V |
| 60227IEC06 (RV) | 300/500 V |
| 60227IEC08 (RV-90) | 300/500 V |
| 60227IEC52 (RVV) | 300/300 V |
| 60227IEC53 (RVV) | 300/500 V |
| RVVP | 300/300 V |
| RVS | 300/300 V |
| ZC-BV / ZR-BV | 450/750 V |
| ZCN-BV / NH-BV | 450/750 V |
Continuous conductor temperature: 70°C for standard products; 90°C for BV-90 and RV-90. Installation ambient temperature at least 0°C. BV and BVR bending radius: at least 4D when outside diameter is no more than 25 mm, otherwise 6D.